76 Subject to technical alterations BU 0200 GB
3.4.4 PROFIBUS DP, SK CU4-PBR
Up to four connected frequency inverters can be managed by the internal PROFIBUS DP module (control,
status messages, parameterisation and diagnosis).
Baud rate: max. 12 MBaud
Protocol: DPV 0 and DPV 1
2x digital inputs
Automatic detection: PPO type, baud rate
DIP switches for: addressing, bus termination
Status LEDs: Module status, module error, bus
status, bus error, Dig. In 1, Dig. In 2
The terminal block of the Customer Unit SK CU4-PBR… is divided into two potential levels.
Up to 2 sensors can be connected via the terminal block (terminals C1 and C2).
NOTE
Looping of the 24V supply voltage (terminals 40/44) is in principle possible, however, a
maximum current load of
2A for the SK CU4-PBR must not be exceeded!
Detailed information about operation via PROFIBUS DP can be found in the relevant supplementary manual
BU0220.
- www.nord.com
-
46 81 82 47 83 46 81 82 44 40 78 77 C2 C1 40 44
PBR A
PBR B
PBR A
PBR B
Sys+
Sys-
GND B
GND B
VP +5V
Incoming
PROFIBUS DP cable
Outgoing
PROFIBUS DP cable
Connection of the 24V supply volt-
age from the SK 200E
System bus connection
from the SK 200E
Potential level: System bus
Potential level:
Field bus
24V
GND
Connection to the
terminal block of the SK CU4-PBR