6 Parameterisation
BU 0200 GB Subject to technical alterations 201
Parameter Setting value / Description / Note Device Supervisor
Parameter
set
P173 Option status (Module status)
0 ... FFFF (hex)
Possible displayed values:
Bit 0 = not used
Bit 1 = not used
Bit 2 = not used
Bit 3 = not used
Bit 4 = not used
Bit 5 = not used
Bit 6 = System bus “BUS WARNING”
Bit 7 = System bus “BUS OFF”
Bit 8 = Status FI1 (Low - Bit)
Bit 9 = Status FI1 (High - Bit)
Bit 10= Status FI2 (Low - Bit)
Bit 11= Status FI2 (High - Bit)
Bit 12= Status FI3 (Low - Bit)
Bit 13= Status FI3 (High - Bit)
Bit 14= Status FI4 (Low - Bit)
Bit 15= Status FI4 (High - Bit)
Status for FIx:
BIT High BIT Low Meaning
0 0 FI is offline
0 1 unknown FI
1 0 FI is online
1 1 FI lost (switched off)
P174 State of digital inputs
0 ... 15 Instantaneous image of input level logic of the digital inputs.
Possible displayed values:
Bit 0= Input 1 ((DIN1) (of the BUS module))
Bit 1= Input 2 ((DIN2) (of the BUS module))
Bit 2= Input 3 ((DIN3) (of the BUS module))
Bit 3= Input 4 ((DIN4) (of the BUS module))
P175 State of relays
SK TU4-IOE
0 ... 3 Instantaneous image of output level logic of the digital output.
Possible displayed values:
Bit 1= Output 1 ((DO1) (of the BUS module))
Bit 2= Output 2 ((DO2) (of the BUS module))
P176 ... [-01]
...
... [-03]
Current voltage
Displays the voltage level of the signals at the analog inputs/outputs of the I/O extension
module.
0.0 ... 10.0 V
… [-01] = Actual voltage (AIN1)
… [-02] = Actual voltage (AIN2)
… [-03]
= Actual voltage (AOUT)