Combination Fire Alarm/Burglary Systems
PN 15842:K 7/23/2002 83
APPENDIX T Combination Fire Alarm/Burglary
Systems
ACS annunciators can be used in combination fire/burglary and burglary
systems within the requirements set forth in this appendix.
1. Shielded cable must be used on all input/output wiring. Terminate both
ends of the shield at earth ground.
2. The annunciators shall be mounted within the protected area.
3. A pair of LEDs shall be set up to indicate the status of the zones covered in
a given premise and for the arm/disarm status.
4. Further requirements governing installation and programming are covered
in manuals for individual control panels (see Section 1.2 “Related
Documentation” for part numbers).