Installation, Configuration, and Programming
32 PN 15842:K 7/23/2002
4.8 Earth Ground
Connect Earth Ground to a mounting screw on the backbox or cabinet During
mounting (see Section 4.3), the backbox or cabinet should have been connected
to a solid earth ground such as a cold water pipe.
ACM-24AT, ACM-48A: Ground is on the EIA-485 terminal block.
ACM-16AT and ACM-32A: Ground is on the Power terminal block.
4.9 Main Power Supply Connections
The ACS power source must be filtered, non-resettable, 24 VDC listed for fire-
protective signalling use. Sources include main power supplies, auxiliary power
supplies, and on-board power supplies (integral to fire alarm control panel).
The power run to the annunciator need not contain a Power Supervision Relay
because loss of power is inherently supervised through communication loss
(loss of EIA-485 communication is registered at the control panel during loss of
power to the annunciator).
See accompanying figures for power supply diagrams:
Section 4-13 “Power Circuit for ACM-24AT and ACM-48A”.
Section 4-14 “Power Circuit for ACM-16AT and ACM-32A”.
For details about connections to particular control panels, see the appropriate
appendix in this manual.
Note: All power must be turned off when connecting the 24 VDC power to the
annunciator. Reapply power according to the instructions in your control panel
manual.

Table of Contents

Other manuals for Notifier ACM-24AT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier ACM-24AT and is the answer not in the manual?

Notifier ACM-24AT Specifications

General IconGeneral
BrandNotifier
ModelACM-24AT
CategoryFire Alarms
LanguageEnglish

Related product manuals