NFS-3030 Systems
PN 15842:K 7/23/2002 87
APPENDIX V NFS-3030 Systems
V.1 Capabilities
When installed with an NFS-3030, annunciators can be programmed to
annunciate the status of addressable devices, general zones, logic zones, and
several system control functions:
Devices
Intelligent Detectors
Monitor and Control Modules
Addressable Manual Pull Stations
Wireless Devices
Panel Circuit Modules
Note: Refer to the appropriate FACP manuals for more information.
Zones 0-999
Logic Zones 1-1000
System Controls
Acknowledge
Signal Silence
System Reset
•Lamp Test
•Drill
Disable
Monitor
Control
Telephone
XP Series Transponder System
Power and Audio Supply Supervision
XP Series Form-C Alarm and Trouble Relays
Control, Monitor, and Relay Module Circuits
V.2 Connecting the EIA-485 Circuit
One ACS circuit may
be connected to the
NFS-3030 as shown in the
accompanying illustration. The
NFS-3030 must be at the end of the
EIA-485 circuit.
See Section 3.3 “EIA-485 Wiring
Specifications” for details and notes
about EIA-485 requirements.
+
-
3030-ACS-TB7.cdr
TB7 on NFS-3030

Table of Contents

Other manuals for Notifier ACM-24AT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier ACM-24AT and is the answer not in the manual?

Notifier ACM-24AT Specifications

General IconGeneral
BrandNotifier
ModelACM-24AT
CategoryFire Alarms
LanguageEnglish

Related product manuals