Figure 3.12 Custom Tone Example
PULSE ON TIME: The Pulse On time is the amount of time that the tone will be ON within a
Period. Press this softkey to enter the amount of time in second and fraction of a second increments.
PERIOD: A Period is the length of time designated for a pulse, including Pulse On time and
Pulse Off time. The pulse off time is designated by the amount of time left in a Period after the
Pulse On time has expired. Press this softkey to enter the amount of time in second and fraction of
a second increments.
NUMBER OF PULSES: Press this softkey to enter the number of pulses that will occur before
the Tone Off Period.
TONE OFF PERIOD: The Tone Off Period is the amount of time that the tone will be silent
before running the pulse pattern again. Press this softkey to enter the amount of time in seconds and
fraction of a second increments.
For more information on programming the Intelligent Sounder Base, refer to “Detector Point” on
page 47.
Pressing the MORE soft key on this Panel Settings screen will display this screen:
Figure 3.13 Panel Settings (4) Screen
PANEL SETTINGS
SILENCEABLE WATERFLOW: NO
MN PRIORITY OVER FIRE: YES
SOUNDER BASE STANDBY POWER MON: OFF MORE
MN CONTROL: SUBSIDIARY ACCEPT
RF WEAK LINK FAULT REMINDER: ON BACK