28 AFP-3030 Programming Manual — P/N DOC-01-032:A 26/06/2015
PrealarmProgram Panel Program
SILENCEABLE WATERFLOW: If the SILENCEABLE WATERFLOW option is set to NO,
incoming Waterflow events will not be allowed to be silenced. If set to
YES, incoming Waterflow
events can be silenced. Default:
NO
MN PRIORITY OVER FIRE: If the MN PRIORITY OVER FIRE option is set to NO,
Fire events will have a higher priority than Mass Notification (MN) events. If set to
YES, MN
events will have a higher priority than Fire events. If set to
MN NOT USED, this system is being
used for fire protection only.
SOUNDER BASE STANDBY POWER MON: If the SOUNDER BASE STANDBY
POWER MON
option is set to ON, external power on the sounder base will be monitored when in
standby. If set to
OFF, external power on the sounder base will not be monitored when in standby.
Set to ON when the sounder base is powered by a constant 24 VDC. Default:
OFF
MN CONTROL: Toggle between SUBSIDIARY, ACU, LOC, and CSS. This option should remain
subsidiary if the AFP-3030 is not in Network Control Mode. If SUBSIDIARY: Select subsidiary if
the AFP-3030 does not have an associated DVC set as an ACU, LOC, or CSS. If ACU, LOC, or CSS:
Select ACU, LOC, or CSS to match the configuration programming of an associated DVC used for
Mass Notification. Default: SUBSIDIARY
RF WEAK LINK FAULT REPORTING: Toggle between ON and OFF. If ON: The AFP-3030 will
report a fault when a wireless device loses communication with the wireless gateway. If OFF: The
AFP-3030 does not report communication loss of the wireless devices to the wireless gateway.
Default: ON
Pressing the MORE soft key on this Panel Settings screen will display this screen:
Figure 3.14 Panel Settings (5) Screen
PHOTO/CO (PHOTO/SUP) LATCHING: Only applies to Photo/CO detectors programmed as
PSUP: Toggle between YES and NO. This option will allow the photo element of any PSUP detec
-
tors on the fire panel to be latching or tracking. If NO: The photo element of all PSUP detectors will
be tracking. If YES: The photo element of all PSUP detectors will be latching. Default: NO
PANEL SETTINGS
PHOTO/CO (PHOTO/SUP) LATCHING: YES
ACCEPT
BACK

Table of Contents

Other manuals for Notifier AFP-3030

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP-3030 and is the answer not in the manual?

Notifier AFP-3030 Specifications

General IconGeneral
BrandNotifier
ModelAFP-3030
CategoryControl Panel
LanguageEnglish

Related product manuals