38 AFP-3030 Programming Manual — P/N DOC-01-032:A 26/06/2015
PrealarmProgram Panel Program
ACM-PSI Point Mapping
Refer to the following table for ACM-PSI predefined points:
AXXP03 Relay Output 3 Monitor -
Zone 3
Relay will energise when Zone 3 on the local fire panel is active.
AXXP04 Relay Output 4 Monitor -
Zone 4
Relay will energise when Zone 4 on the local fire panel is active.
AXXP05 Relay Output 5 Monitor -
Zone 5
Relay will energise when Zone 5 on the local fire panel is active.
AXXP06 Relay Output 6 Monitor -
Zone 6
Relay will energise when Zone 6 on the local fire panel is active.
AXXP07 Relay Output 7 Monitor -
Zone 7
Relay will energise when Zone 7 on the local fire panel is active.
AXXP08 Relay Output 8 Monitor -
Zone 8
Relay will energise when Zone 8 on the local fire panel is active.
ACS Point: Point Text: Point Type: Explanation:
Table 3.5 ACS Point Mapping: Explanation of ACM-8RA Point Modes (2 of 2)
ACS Point: Point Text: Point Type: Explanation:
AXP1 Battery Test N/A A battery test request was received from the fire panel. This point should be
mapped to logic zone ZL980 programmed with the following equation:
TIM(MO,WE,FR,06:00:00,07:00:00)
This equation will activate the logic zone between 6:00AM and 7:00AM every
Monday, Wednesday, and Friday.
AXP2 High Current Mode N/A A high current mode message was received from the fire panel
AXP3 NAC 1 Activate N/A A NAC 1 output active request was received from the fire panel
AXP4 NAC 2 Activate N/A A NAC 2 output active request was received from the fire panel. This point should be
mapped to a logic zone programmed with the following equation:
OR(Z0)
When an alarm occurs, general alarm zone 0 will activate, activating the logic zone. If
additional alarms on other nodes are to be included, the logic equation can be
modified as follows:
OR(Z0,NxxxZ0) where xxx is the node number of the remote node.
AXP5 Alarm Routing Output N/A An A.R.E. Alarm Routing active request was received from the fire panel
AXP6 System Fault Output N/A An A.R.E. System Fault output request was received from the fire panel
AXP7 Sys Disabled Output N/A An A.R.E. System Disabled output request was received from the fire panel
AXP8 Program Output 1 Non-Fire An A.R.E. Programmable output 1 request was received from the fire panel
AXP9 Program Output 2 Non-Fire An A.R.E. Programmable output 2 request was received from the fire panel
AXP10 Program Output 3 Non-Fire An A.R.E. Programmable output 3 request was received from the fire panel
AXP11 NAC 1 S/C Fault Fault An ACM NAC 1 Short Circuit Fault has occurred
AXP12 NAC 2 S/C Fault Fault An ACM NAC 2 Short Circuit Fault has occurred
AXP13 NAC 1 O/C Fault Fault An ACM NAC 1 Open Circuit Fault has occurred
AXP14 NAC 2 O/C Fault Fault An ACM NAC 2 Open Circuit Fault has occurred
AXP15 NAC 1 Overload Fault Fault An ACM NAC 1 Overload Fault has occurred
AXP16 NAC 2 Overload Fault Fault AN ACM NAC 2 Overload Fault has occurred
AXP17 Earth Fault Fault An ACM Earth Fault has occurred
AXP18 A.R.E. Alarm Routed Non-Fire An A.R.E. Alarm Routed input activated
Table 3.6 ACS Point Mapping: Explanation of ACM-PSI Point Modes (1 of 2)