AFP-3030 Programming Manual — P/N DOC-01-032:A 26/06/2015 73
Autoprogram Menu PrealarmProgram
Add New Points
When the REVIEW soft key is pressed, the panel will individually display each new SLC point
found during autoprogramming. The screen below uses an SLC detector point as an example.
Figure 3.61 Autoprogram Confirmation Screen (New SLC Point)
Soft Keys
YES: Press this soft key to install the new point into the panel’s database.
EDIT: Press this soft key to advance to the point programming menu for the new point.
NO: Press if the point will not be installed.
Error and Discrepancy Resolution
Pressing the REVIEW soft key will bring up screens that provide the means to resolve any errors or
discrepancies found during autoprogram.
Figure 3.62 Autoprogram Confirmation Screen (Missing Point)
Display
This screen will display the SLC device address when a previously installed/programmed point
does not respond during a subsequent Autoprogram.