74 AFP-3030 Programming Manual — P/N DOC-01-032:A 26/06/2015
PrealarmProgram Autoprogram Menu
Soft Keys
YES: Press to delete the point information from the panel’s database.
NO: Press to leave the point information in the panel’s database.
Figure 3.63 Autoprogram Confirmation Screen (Mismatched Point)
Display
The OLD field contains the information currently in the panel’s programming database. The NEW
field contains the information found during autoprogramming. The fields contain the FlashScan
Type ID codes if the device is FlashScan, or they will contain the device type if CLIP.
Soft Keys
YES: Press this soft key to accept the new device type.
EDIT: This soft key will appear only when SLC devices are mismatched. Press it to advance to the
point programming screen for this point.
NO: Press if the new information should not be installed over the existing information in the database.
Figure 3.64 Autoprogram Confirmation Screen (Double Address)
Display
The SLC loop number and device address are displayed where the Autoprogram has found more
than one detector or module with the same address.
AUTOPROGRAM CONFIRMATION
MISMATCHED MODULE FOUND AT L01M123
OLD:CONTROL
NEW:MONITOR
ACCEPT CHANGES?
YES NO
EDIT BACK
AUTOPROGRAM CONFIRMATION
DOUBLE ADDRESS FOUND AT LXXDXXX
ACCEPT
BACK

Table of Contents

Other manuals for Notifier AFP-3030

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP-3030 and is the answer not in the manual?

Notifier AFP-3030 Specifications

General IconGeneral
BrandNotifier
ModelAFP-3030
CategoryControl Panel
LanguageEnglish

Related product manuals