EasyManua.ls Logo

Notifier AM-6000 - Class A Wiring Circuit

Notifier AM-6000
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CLASS “A” WIRING CIRCUIT AND LINE ISOLATORS
Functions in accordance with NFPA STYLE 7 Signaling Line Circuit
»
Note: the number of addressable devices between ISO-X modules must not exceed 25 devices.
OPERATION
By separating each group of SLC Loop devices, with a pair of ISO-X Trouble Isolator Modules , each device is protected
from opens and short circuits on all other sections.
For instance, a trouble on Section 2 will not affect Section 1 and 3.
The Isolator Modules on either side of Section 2 will open the SLC Loop. Section 1 will still operate from power on Channel
A, and Section 3 will operate from Channel B.
Since the control panel will no longer be able to communicate with the SLC Loop devices on Section 2, a trouble signal will
be generated (INVALID REPLY from Section 2 Points).
This circuit is a variation of an NFPA Style 6 Signaling Line Circuit, therefore no T-Tapping or branching is allowed.
The ratings and characteristics are the same as for the Style 6 circuit.
AM-6000-60001.VP Installation Manual Page 16
Doc. M-180.2-AM6000-ENG Rev. B.1 NOTIFIER ITALIA
ISO-X Isolator Module
Protected premises - Section 2
ISO-X Isolator Module
ISO-X Isolator Module
ISO-X Isolator Module
Protected premises - Section 1
Protected premises - Section 3
CHANNEL A CHANNEL B
(Outward) (Return)

Related product manuals