INERTIA-2464
Technical & Programming Manual Page 23
Copyright (c) 1996,
INERTIA FIRE SYSTEMS
ISOLATE
ISOLATE
#
ENTER
The isolate function prevents the transmission of alarms or faults from the zones to the master alarm facility.
The character "#" in the keystroke requires any one of the following entries;
1,2,3,4........, 63,64 or "ALL"
If only one zone is to be isolated, use the appropriate zone number. Alternatively the "ALL" button can be used
to simultaneously isolate all zones.
To isolate a particular zone or all zones;
1. Press the "ISOLATE" button.
The buzzer will give 2 short beeps to indicate that isolate mode has been entered.
2. The LCD display will read "ALARM ISOL. MODE, ENTER ZONE No.".
3. Enter the zone number ("#").
4. Press "ENTER".
A long beep will signify an incorrect entry and will revert back to normal operating mode. The "ISOLATE"
button will need to be depressed again to re-enter isolate mode.
If a correct entry is made, the zone is immediately isolated. If the zone is already in alarm, all of its alarm
outputs are isolated and indicators remain visible.
If the "ALL" function is performed, all zones will be isolated, regardless of their previous state. Performing the
"ALL" function for a second time will de-isolate all zones.