EasyManuals Logo

Notifier INERTIA-2464/64 User Manual

Notifier INERTIA-2464/64
62 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #6 background imageLoading...
Page #6 background image
Page 2
INERTIA-2464
Technical & Programming Manual
Copyright (c) 1996,
INERTIA FIRE SYSTEMS
SPECIFICATION
Cabinet Zinc Sealed Steel 1.6mm
Powder Coated
Hinged Inner Door
Hinged Outer Door
Outside Dimensions 2464/24 750mm H x 390mm W x 160mm D
2464/32>64 750mm H x 780mm W x 160mm D
Battery Box 280mm H x 390mm W x 160mm D
AC Operational Voltage 240 VAC 50Hz + 10% Australian Version
200 or 220 VAC 50Hz + 10% Hong Kong Version
220 VAC 50Hz + 10% Chinese Version
Internal Power Supplies 24 VDC 3.0AMP in 8, 16, 24, 32, 40, 48, 56, 64 zones
5 VDC 2.0AMP
Microprocessor 80C52
Memory Type Non-volatile E2ROM
Liquid Crystal Display 2 Lines x 16 Characters LED Backlit
Fuses F1: Door Holder 3AG 3A
F2: AC Input M205 6.3A
F3: AUX & Mimic 3AG 1A
F4: ACF 3AG 1A
F5: Bell 3AG 1A
E.O.L Resistor On AZF's 4K7 Ohms