INERTIA-2464
Technical & Programming Manual Page 29
Copyright (c) 1996,
INERTIA FIRE SYSTEMS
PROGRAM MODE
TO ENTER PROGRAM MODE
Hold the door switch down while pressing the following buttons in order shown to enter programming mode.
PREVIOUS
NEXT
SELECT
EXIT
ENTER
PROGRAMMING MODE
The liquid crystal display will display all messages and prompts required to program the 2464
ONLY the "PREVIOUS","NEXT","SELECT","EXIT" AND "ENTER" keys are used in programming mode. All
other keys will give an error beep and are ignored.
You must exit programming mode if any other panel functions are to be performed.
Note: Refer to appendices for detailed explanation of functions
PROGRAMMING HIERARCHY
EXIT
SAVE CHANGES
YES NO
ZONES RELAY
GLOBAL PRINT
ZONES
TYPE OUTPUT
STD LATCHING INDICATE
STANDARD LATCHING AVF I BELL
NON LATCH IB GENERAL
NON LATCH 20S IBG ACF OUT
TIME DELAY 10S (RESETTING) IBGA BRIGADE 1
TIME DELAY 20S (RESETTING) IBGA BRIGADE 2
TIME DELAY 30S (RESETTING) IBGA BRIGADE 1 & 2
TIME DELAY 40S (RESETTING)
TIME DELAY 50S (RESETTING)
TIME DELAY 60S (RESETTING)