Page 4
INERTIA-2464
Technical & Programming Manual
Copyright (c) 1996,
INERTIA FIRE SYSTEMS
Additional relay outputs:
Relays Qty Hardware Required Product Code
8 1 Relay board containing 8 relays PCB-803
16 2 Relay board containing 8 relays PCB-803
24 3 Relay board containing 8 relays PCB-803
32 4 Relay board containing 8 relays PCB-803
40 5 Relay board containing 8 relays PCB-803
48 6 Relay board containing 8 relays PCB-803
56 7 Relay board containing 8 relays PCB-803
64 8 Relay board containing 8 relays PCB-803
Open Collector Outputs 24VDC 1A each:
Relays Qty Hardware Required Product Code
8 1 Open collector output board 8 outputs 24VDC 1A each. PCB-813
16 2 Open collector output board 8 outputs 24VDC 1A each. PCB-813
24 3 Open collector output board 8 outputs 24VDC 1A each. PCB-813
32 4 Open collector output board 8 outputs 24VDC 1A each. PCB-813
40 5 Open collector output board 8 outputs 24VDC 1A each. PCB-813
48 6 Open collector output board 8 outputs 24VDC 1A each. PCB-813
56 7 Open collector output board 8 outputs 24VDC 1A each. PCB-813
64 8 Open collector output board 8 outputs 24VDC 1A each. PCB-813
ENVIRONMENTAL LIMITS
-10 Deg. C to +55 Deg. C Dry heat.
+40 Deg. C @ 93% Relative Humidity.
POWER SUPPLY RATINGS AND SETTINGS
27VDC 3A POWER SUPPLY
This supply's primary function is to power all external operations of the FIP, ie: Detection circuits, Ancillary
circuits, Charge batteries etc. This supply meets the requirements of AS1603.4 with the panel for up to 64
zones.