72 NFS2-3030 Operations Manual — P/N 52546:N1 06/20//2014
Printing Reports Print Programming Menu Screen (2)
LCD DISPLAY: Press to print information about backlight handling during fire alarm, backlight
intensity, and display language. The report looks like this:
5.3 Print Programming Menu Screen (2)
The second PRINT PROGRAMMING MENU screen displays when MORE is pressed at the first
PRINT PROGRAMMING MENU screen:
Figure 5.3 Print Programming Screen
Soft Keys
SUPERVISION: Press to print information on power supply and printer monitoring. The report
looks like this:
******PANEL TIMERS**************************************************************
VERIFY TIME: 30 VERIFY=PREALARM: NO
MAXIMUM VERIFICATION COUNT: 00
AC FAIL DELAY: 8 HOURS
SILENCE INHIBIT: 00:00
AUTO SILENCE: 10 MINUTES
PAS OFF
PRESIGNAL DELAY 03:00
********************************************************************************
******LCD DISPLAY***************************************************************
LCD INTENSITY: 040 BACKLIGHT: ON
LANGUAGE: ENGLISH
********************************************************************************
PRINT PROGRAMMING MENU
SUPERVISION EVENT LOGGING
CUSTOM ACTION MESSAGES
BACK
******SUPERVISION***************************************************************
MAIN POWER SUPPLY ADDRESS: L01M006
PRINTER: 80-column
TAMPER INPUT: NO
AUXILIARY TROUBLE: NO
********************************************************************************

Other manuals for Notifier NFS2-3030

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier NFS2-3030 and is the answer not in the manual?

Notifier NFS2-3030 Specifications

General IconGeneral
TypeIntelligent Fire Alarm Control Panel
Power Supply (6 amps total system power)6 amps total system power
SLC Loop Voltage24V DC
NAC Voltage24V DC
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity Range10% to 93% non-condensing
Network CapabilityYes, via NOTI-FIRE-NET
ProgrammingVia VeriFire Tools
Power Supply120V or 240V AC, 50/60 Hz
Battery BackupYes
Communication PortsRS-232, USB
SLC Loops1 or 2
NAC Outputs4
Operating Voltage24V DC nominal
Number of Signaling Line Circuits (SLC)2
SLC Loop Current0.5 A max per loop
Number of Notification Appliance Circuits (NAC)4
Total NAC Current6 amps
Number of Relays4
Relay Contact Rating2.0 A @ 30 VDC