NFS2-3030 Operations Manual — P/N 52546:N1 06/20//2014 21
The Main Menu General Information
Line 14
PEAKS: 56% - This value represents the highest percent per foot obscuration reading taken
by this detector. It can be a historical figure, and does not necessarily represent the highest
reading for this particular alarm. Re-initializing the detector would reset this value to zero.
VERIFY COUNT: 02 - This displays the number of times the detector has gone into
alarm. This count aids in differentiating false alarms from actual alarms by showing repeated
alarm events that have come into the device. In this example, the detector has gone into alarm
two times since the verification count was begun. The FACP will signal a trouble condition
when the verify count is exceeded. Displays as
COUNT for FSC-851 IntelliQuad and
aspiration detectors.
CO-OP: D100,158 - Indicates the address(es) of any detector(s) linked with the detector
that’s in alarm for Co-operative Multi-alarm Sensing. This field does not display for
Acclimate, FSC-851 IntelliQuad, FCO-851 detectors, Beam detectors or Heat detectors.
CO: - FSC-851 IntelliQuad and FCO-851 detectors only, FlashScan only - Carbon Monoxide
reading in parts per million.
TEMP: -Displays degrees Centigrade for Acclimate, FSC-851, FCO-851, heat, and
aspiration detectors
Line 15 - The current time and date are displayed in this line.
Line 16
BACK - Press to return to the previous screen.
1.8.3 Multiple Event List
Pressing the Multiple Event List soft key shows off-normal events simultaneously in groups of
eight. One event is shown at the top, and seven are shown in the list below it. The list will consist of
the events immediately following the event at the top, with the priority of event types determined
by the programmed Event Ordering setting (USA or Canada)
Using the Next Selection/Previous Selection special function keys to scroll through the list will
replace the event at the top of the screen with the first event in the series displayed below it.
With Fire as the highest priority: With MNS as the highest priority:
USA Event Order Canada Event Order USA Event Order Canada Event Order
Fire Fire MN Alarm MN Alarm
MN Alarm MN Alarm Fire Fire
CO Alarm CO Alarm CO Alarm CO Alarm
CO Pre-alarm CO Pre-alarm CO Pre-alarm CO Pre-alarm
Security Security
Supervisory Supervisory MN Supervisory MN Supervisory
MN Supervisory MN Supervisory Supervisory Supervisory
Trouble Trouble MN Trouble MN Trouble
MN Trouble MN Trouble Trouble Trouble
Pre-alarm Pre-alarm Pre-alarm Pre-alarm
Disabled Disabled Disabled Disabled
Note: Fire/MNS priority dependent on programming. Refer to the fire panel programming manual for
additional information.

Other manuals for Notifier NFS2-3030

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier NFS2-3030 and is the answer not in the manual?

Notifier NFS2-3030 Specifications

General IconGeneral
TypeIntelligent Fire Alarm Control Panel
Power Supply (6 amps total system power)6 amps total system power
SLC Loop Voltage24V DC
NAC Voltage24V DC
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity Range10% to 93% non-condensing
Network CapabilityYes, via NOTI-FIRE-NET
ProgrammingVia VeriFire Tools
Power Supply120V or 240V AC, 50/60 Hz
Battery BackupYes
Communication PortsRS-232, USB
SLC Loops1 or 2
NAC Outputs4
Operating Voltage24V DC nominal
Number of Signaling Line Circuits (SLC)2
SLC Loop Current0.5 A max per loop
Number of Notification Appliance Circuits (NAC)4
Total NAC Current6 amps
Number of Relays4
Relay Contact Rating2.0 A @ 30 VDC