NFS2-3030 Operations Manual — P/N 52546:N1 06/20//2014 69
Section 5: Printing Reports
A variety of reports can be generated and printed from the NFS2-3030. Reports listing all event,
alarm, trouble, supervisory, or security history can be generated from the history screens in
Section 4, “Viewing and Printing History Information”, on page 65. The following section
describes how to print programming, Walk Test, and active point information.
5.1 Printer Functions Screen
The following screen displays when the Printer Functions soft key is pressed at the Main
Menu. This key will appear only if a printer has been selected through programming.
Figure 5.1 Printer Functions Screen
Soft Keys
PROGRAMMING: Press this soft key to display the Print Programming Menu screen.
ACTIVE POINTS: Press this soft key to display the Active Points Menu screen.
WALK TEST: Press this soft key to print point activations for the last Walk Test performed. The
report looks like this:
NOTE: Report formats are shown below as printed by an 80-column printer. When these reports
are printed on a Keltron, which is a 40-column printer, the formats are the same except they are
displayed on two lines instead of one.
LAKEVIEW GENERAL HOSPITAL
SYSTEM NORMAL
10:22:34A TUE JAN 25, 2011
PRINTER FUNCTIONS
PROGRAMMING
ACTIVE POINTS INSTALLED POINTS
WALK TEST
DETECTOR MAINTENANCE REPORT BACK
******WALK TEST RESULTS*********************************************************
TEST NO ANSWER DETECTOR 73
Z003 SMOKE(ION) 02:54:04P WED MAR 9,2011 L01D073
TEST FIRE ALARM ROOM 101 1ST FLOOR
Z001 HEAT 02:54:31P WED MAR 9,2011 L01D003
TEST FIRE ALARM ROOM 221 2ND FLOOR
Z001 SECURITY L 02:54:59P WED MAR 9,2011 L01M004
TEST ACTIVE LAB 3RD FLOOR
Z004 CONTROL 02:55:09P WED MAR 9,2011 L01M005

Other manuals for Notifier NFS2-3030

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier NFS2-3030 and is the answer not in the manual?

Notifier NFS2-3030 Specifications

General IconGeneral
TypeIntelligent Fire Alarm Control Panel
Power Supply (6 amps total system power)6 amps total system power
SLC Loop Voltage24V DC
NAC Voltage24V DC
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity Range10% to 93% non-condensing
Network CapabilityYes, via NOTI-FIRE-NET
ProgrammingVia VeriFire Tools
Power Supply120V or 240V AC, 50/60 Hz
Battery BackupYes
Communication PortsRS-232, USB
SLC Loops1 or 2
NAC Outputs4
Operating Voltage24V DC nominal
Number of Signaling Line Circuits (SLC)2
SLC Loop Current0.5 A max per loop
Number of Notification Appliance Circuits (NAC)4
Total NAC Current6 amps
Number of Relays4
Relay Contact Rating2.0 A @ 30 VDC