NFS2-3030 Operations Manual — P/N 52546:N1 06/20//2014 71
Print Programming Menu Screen Printing Reports
5.2 Print Programming Menu Screen
This screen displays when the PROGRAMMING soft key is pressed on the PRINTER FUNCTIONS
screen. Refer to Figure 5.1 on page 69).
Figure 5.2 Print Programming Screen
Soft Keys
NETWORK PARAMETERS: Press to print node number, node label, Channel A and B threshold,
network style. The report looks like this:
SETTINGS: Press to print broadcast time, event ordering, and block acknowledge. The report
looks like this:
TIMERS: Press to print timer values for Auto Silence, Silence Inhibit, AC Fail Delay time and
whether it has been enabled, Proprietary Reminder, and Remote Reminder timers. The report looks
like this:
PRINT PROGRAMMING MENU
NETWORK PARAMETERS LCD DISPLAY
SETTINGS
TIMERS MORE
BACK
******NETWORK PARAMETERS********************************************************
NODE:N124 STYLE 7 NO
NODE LABEL: LAKEVILLE GENERAL HOSPITAL
CH A. THRESHOLD: HIGH CH B. THRESHOLD: HIGH
IP ACCESS:OFF
********************************************************************************
******PANEL SETTINGS************************************************************
LOCAL CONTROL: NO TROUBLE REMINDER: YES
PIEZO: ON POWER MANAGEMENT MODE: OFF
PROPRIETARY SUPERVISING STATION: NO
EVENT ORDERING: USA
DISPLAY ADDRESS: YES
DC C PA RTI CI PAT IO N: NO
REGIONAL SETTING DEFAULT
LCM LOCAL MODE: NO
RAPID ALL CALL: NO
SILENCEABLE WATERFLOW: NO
MN PRIORITY OVER FIRE: YES
DRILL CONFIGURATION: AUDIBLE AND VISIBLE
SILENCE CONFIGURATION: AUDIBLE
********************************************************************************

Other manuals for Notifier NFS2-3030

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier NFS2-3030 and is the answer not in the manual?

Notifier NFS2-3030 Specifications

General IconGeneral
TypeIntelligent Fire Alarm Control Panel
Power Supply (6 amps total system power)6 amps total system power
SLC Loop Voltage24V DC
NAC Voltage24V DC
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity Range10% to 93% non-condensing
Network CapabilityYes, via NOTI-FIRE-NET
ProgrammingVia VeriFire Tools
Power Supply120V or 240V AC, 50/60 Hz
Battery BackupYes
Communication PortsRS-232, USB
SLC Loops1 or 2
NAC Outputs4
Operating Voltage24V DC nominal
Number of Signaling Line Circuits (SLC)2
SLC Loop Current0.5 A max per loop
Number of Notification Appliance Circuits (NAC)4
Total NAC Current6 amps
Number of Relays4
Relay Contact Rating2.0 A @ 30 VDC