NFS2-3030 Operations Manual — P/N 52546:N1 06/20//2014 81
Alphabetical List Software Type ID Codes
WATERFLOW Monitor for waterflow alarm switch
WATERFLOW S Monitor for supervisory condition for activated waterflow switch
WEATHER ALRT Monitor for weather condition, tracking
*Not suitable for Canadian applications.
**Subject to AHJ approval.
Software Type ID Code Device
Table A.1 Software Type ID Codes, Alphabetical List (4 of 4)

Other manuals for Notifier NFS2-3030

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier NFS2-3030 and is the answer not in the manual?

Notifier NFS2-3030 Specifications

General IconGeneral
TypeIntelligent Fire Alarm Control Panel
Power Supply (6 amps total system power)6 amps total system power
SLC Loop Voltage24V DC
NAC Voltage24V DC
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity Range10% to 93% non-condensing
Network CapabilityYes, via NOTI-FIRE-NET
ProgrammingVia VeriFire Tools
Power Supply120V or 240V AC, 50/60 Hz
Battery BackupYes
Communication PortsRS-232, USB
SLC Loops1 or 2
NAC Outputs4
Operating Voltage24V DC nominal
Number of Signaling Line Circuits (SLC)2
SLC Loop Current0.5 A max per loop
Number of Notification Appliance Circuits (NAC)4
Total NAC Current6 amps
Number of Relays4
Relay Contact Rating2.0 A @ 30 VDC