72
Menu
Sub-Menu
Parameter
Description Value
Default
Setting
6 2 2
Slope of Outdoor Reset Curve
0.2 -0.8 0.6 (low temperature)
0.4 - 3.5 1.3 (high temperature)
See graph and description of Parameter 422.
6 2 3
Parallel Shift of Reset Curve
-12 - +12 (when 4.2.0 = 0)
0
-25 - +25 (when 4.2.0 = 1)
See description of Parameter 423.
6 2 4
Room Sensor Inuence 0 - 20
2 if Parameter 4.2.0 = 0
4 if Parameter 4.2.0 = 1
Adjusts the inuence of room temperature on target boiler temperature - a higher setting causes a greater increase to the boiler
target temperature as the indoor temperature drops below room setpoint. Only applicable when using an optional NTI Room
Sensor and when 6.2.1 = 2 or 4.
6 2 5
MAXIMUM temperature setting
86 - 179 °F 179 if Parameter 6.2.0 = 1
68 - 122 °F 120 if Parameter 6.2.0 = 0
6.2.5 sets the allowable boiler operating temperature range for Zone 3 heating, limiting Automatic Temperature Control and
manual adjustments from the User Menu.
6 2 6
MINIMUM temperature setting
86 - 179 °F 120 if Parameter 6.2.0 = 1
68 - 122 °F 80 if Parameter 6.2.0 = 0
6.2.6 sets the allowable boiler operating temperature range for Zone 3 heating, limiting Automatic Temperature Control and
manual adjustments from the User Menu.
6 3 DIAGNOSTICS
6 3 0 S/W function activation 0 = OFF, 1 = ON 0
Only applicable when using an
NTI room sensor
6 3 1 S/W temperature threshold 50 - 86 °F 68
6 3 4 S/W delay time 0 - 300 minutes 60
6 7 ZONE 3 REGULATION PARAMETERS
6 7 5 Auto Boost 0 = OFF, 1 = ON 0
See description of Parameter
475.
8 SERVICE PARAMETERS
8 0 BOILER STATISTICS-1 - Read Only
8 0 0 3 way valve cycles No. (n x10)
8 0 1 Boiler Pump On Hours (h x10)
8 0 2 Boiler pump cycles No. (n x10)
8 0 3 Boiler Power On Time (h x10)
8 0 4 Fan On Hours (h x10)
8 0 5 Number of fan cycles (n x10)
8 0 6 CH number of ame detections (n x10)
8 0 7 DHW number of ame detections (n x10)
8 1 BOILER STATISTICS-2 - Read Only
8 1 0 CH Burner On Hours (h x10)
8 1 1 DHW Burner On Hours (h x10)
8 1 2 Number Of Flame Faults (n x10)
8 1 3 Number Of Ignition Cycles (n x10)
8 1 4 Average CH Cycle Length (min)
8 1 6 Number of times the Priority Timer (2.10.4) has elapsed, switching priority from DHW to CH (or vice versa).
8 2 BOILER CURRENT STATUS - Read Only
8 2 1 Fan Status 0 = OFF, 1 = ON
8 2 2 Fan Speed RPM
8 2 3 Boiler Pump Status 0 = OFF, 1 or 2 = ON
8 2 4 3 Way Valve Position 0 = DHW, 1 = Central Heating
8 2 5 DHW Flow Rate (in US gpm)
Not applicable to Non-Combi
models
8 2 6 APS Status 0 = Open, 1 = Closed
8 2 8 Gas Power (kW)
Part 9 - Controls