Part 9 - Controls
Menu
Sub-Menu
Parameter
Description Value
Default
Setting
Table 29 - Complete Parameters List
8 3 BOILER CURRENT TEMPERATURES Read Only
8 3 0 CH Supply Setpoint (in °F)
8 3 1 CH Supply Temperature (in °F)
8 3 2 CH Return Temperature (in °F)
8 3 3 DHW Outlet Temperature (in °F)
Not applicable to Non-Combi
models
8 3 4 Exhaust Flue Temperature (in °F)
8 3 5 Outdoor Temperature (in °F)
Only with outdoor sensor
connected
8 4 DHW TANK TEMPERATURE ONLY ACTIVE WITH CONNECTED NTC TANK SENSOR Read Only
8 4 0 Displays current tank temperature (in °F)
Only with NTC tank sensor
connected
8 5 SERVICE
8 5 0
Months to next maintenance 0 - 60 (months) 12
If enabled (8.5.1 = 1), a notication is made on the display (and via the Tele-diagnostic Service, if applicable), warning that it is
time for maintenance
8 5 1 Enable Maintenance advice 0 = OFF, 1 = ON 0
8 5 2
Maintenance Warning Reset Reset? OK= Yes, Esc = No
Resets Maintenance Advice and clears the Warning.
8 5 4 SW Version - Display Interface
8 5 5 SW Version - Main Controller
8 6 ERROR HISTORY
8 6 0
10 last errors ERROR 0 - ERROR 9
This parameter displays the last 10 boiler errors, indicating the error code, day, month and year of occurence.
When the parameter is accessed, the errors are listed from ERROR 0 to ERROR 9.
8 6 1 Error list reset - Clears Error History Reset? OK = yes, ESC = no
8 7 FREE PARAMETERS - Read Only
8 7 0 NOT USED
8 7 1 NOT USED
8 7 2 NOT USED
8 7 3 NOT USED
8 7 4 Boiler ow switch 0= OFF, 1= ON
8 7 6 Safety ame sensor 0= OFF, 1= ON
8 7 8 Boiler power level (%)
0 - 100
(0 = minimum power,
100 = maximum power)
8 7 9 Boiler Flame Signal Measured by the Control
The ame signal must exceed 18
to initially detect the presence of
ame. Flame loss is detected if
the signal drops below 15.