Table 16-14 (d) User Menu (with Buffer Tank selected)
Allows selection of the zone that you would like to view/modify;
options are Z1, Z2, Z3, DHW, DHW Recirc & Buffer Tank.
Note: options extend to Z4, Z5 & Z6 if using an NTI N-Link ZC3
zone controller, or for cascade application.
Buffer Setpoint
(Comfort)
Buffer tank setpoint during Comfort time period. (Range = 50-
190°F)
Buffer Setpoint
(Reduced)
Buffer tank setpoint during Reduced time period. (Range = 50-
190°F)
Scheduling (Control
Mode)
Allows the user to select the type of schedule for heating the
buffer tank. Only applicable when Buffer Tank Function is set as
Fixed Temperature.
Always Off – disabled…boiler ignores buffer tank demands.
Time Program – buffer tank temperature setpoint toggles
between the Comfort and Reduced setpoints according to the
defined time program (see View/Edit Schedule).
Always Active – Buffer tank temperature is always maintained at
the Comfort setpoint.
AUTO Temperature
Control Mode
Allows the user to globally enable/disable the Automatic
Temperature Control Mode.
Room Setpoint
(Holiday/Anti-frost)
Sets the global room temperature setpoint during holiday or
inactive periods. Only applicable when using an NTI Room
Sensor. (Range = 35-75°F)
Operating Mode
(Scheduling*)
See Operating Mode section
* Parameter numbers starting with 4 are for Zone 1; substitute the 4 with a 5 (for Zone 2); 6 (for Zone 3); 14 (for Zone
4); 15 (for Zone 5) or 16 (for Zone 6) for equivalent respect zone parameter.