EasyManua.ls Logo

NTI TFTN - Tech Menu

NTI TFTN
116 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TFTN 085-199 Installation and Operation Manual
77
16.3.2 Tech Menu
All technical parameters of the main controller are accessed from the Tech Menu.
Note: if you have not entered the “ntinetpasscode within the last 30 minutes, you will be asked to enter it again upon
selecting Tech Menu; see Setup Wizard section.
Figure 16-7 Tech Menu
CH Setup - select to access
Central Heating settings
DHW Setup select to
access DHW settings
Cascade Setup select to
access cascade settings or
to set the Boiler Address
Select to access Pump
Control Settings
BMS Control select to
configure the boiler’s
response to an external 0-
10V signal for controlling
the modulation/setpoint
Restore/Backup select to
reset to factory defaults or
to restore/backup settings
from/to the display or
external memory
Complete Menu select to
enter a specific parameter
number or to view the
complete list of parameters
listed numerically
Sensor Configuration
select to configure AUX1
and AUX2 sensor inputs

Other manuals for NTI TFTN

Related product manuals