Service settings manual
Table with description of parameters :
Parameter Function Parameter descri ptio n
Setting range Default
value
S1.1 Hydraulic sche me
Selection of hydraulic scheme.
depends on
controller type
211
S1.2
Code for unlocking the
service setting s
This setting enables the change of code which is
necessary to unlock the service settings.
WARNING!
Keep new code on a safe place. Without this
code is impossible to change service settings.
0000 ÷ 9999
0001
S1.3 Temperature sensor type
Selection of temperature sensors Pt1000 or KTY10.
0 - Pt1000
1 - KTY10
0
S1.4 Temperat ure round up
You set the accuracy of displayed temperatures.
0 - 0.1 °C
1 - 0.2 °C
2 - 0.5 °C
3 - 1 °C
2
S1.5
Period of temperature
logging
By setting this field you define how often the measured
temperatures are saved.
1 - 30 min
5
S1.6
Advanced temperature
screen
Advanced screen means that while checking temperatures
you can see measured and required or calculated tempera-
ture.
0 - basic
1 - advanced
1
S1.7
Automatic shift of clock
to summer/winter time
With the help of a calendar, the controller carries out the
automatic changeover between summer and winter time.
0 - no
1 - yes
1
S1.8
Anti-block function for
pumps and valves
All outputs that haven’t been activated in the last week are
activated on Friday at 20:00 for 10 seconds.
0 - OFF
1 - ON
0
S1.13 Sensor T1 calibration
Correction of displayed measured temperature for sensor
T1.
-5 ÷ 5 K
0
S1.14 Sensor T2 calibration
Correction of displayed measured temperature for sensor
T2.
-5 ÷ 5 K
0
S1.15 Sensor T3 calibration
Correction of displayed measured temperature for sensor
T3.
-5 ÷ 5 K
0
S1.16 Sensor T4 calibration
Correction of displayed measured temperature for sensor
T4.
-5 ÷ 5 K
0
S1.17 Sensor T5 calibration
Correction of displayed measured temperature for sensor
T5.
-5 ÷ 5 K
0