Service settings manual
S2.10
Consider storage tank
temp. 1
We define whether storage tank 1 should be loaded (by
means of collectors) only to the set point temperature.
0 - no
1 - yes
1
S2.11
Consider storage tank
temp. 2
We define whether storage tank 2 should be loaded (by
means of collectors) only to the set point temperature.
0 - no
1 - yes
1
S2.12
Consider storage tank
temp. 3
With settings we define whether storage tank 3 should be
loaded (by means of collectors) only to the set point tempe-
rature.
0 - no
1 - yes
1
S2.13 Min. collector temp.
We define whether and how the minimum collector tempe-
rature is considered.
0 - no
1 - yes
2 - yes, only for
switch-on
2
S2.14
Min. temp. of aux. heat
source Q1
We define whether and how the minimum temperature of
auxiliary heat source Q1 is considered.
0 - no
1 - yes
2 - yes, only for
switch -on
1
S2.15
Min. temp. of aux. heat
source Q2
We define whether and how the minimum temperature of
auxiliary heat source Q2 is considered.
0 - no
1 - yes
2 - yes, only for
switch-on
1
S2.16 Actuator spee d
Actuator running time, needed for a 90° turn. This data is
considered at delayed switchovers with mixing valves.
1 ÷ 8 min
2
S2.17
Regulation constant of the
mixing valve
This setting is PI constant for 3 - point control of mixing
valve.
15 ÷ 60 s
25