EasyManua.ls Logo

Oldham iTrans 2 - Sample Gas Reading via ModBus Network; ModBus Register List

Oldham iTrans 2
106 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
54
IMPORTANT: When commissioning master and slave units on a ModBus
network, it is critical to ensure that every device on the ModBus network
must have a unique address. Otherwise, abnormal behavior of the entire
serial bus can occur.
Sample Gas Reading via ModBus Network
To get a gas reading for Channel 1, you must read register 40102. This
register holds the gas reading in ppm.
Example: Gas reading of 5 ppm = register value of $0005.
Example: Gas reading of 20.9% = register value of $0209.
For Channel 2 you can access the gas reading by looking at register 40202.
For a full list of ModBus commands and registers that are accessible on the
, refer to the next section.
ModBus Register List
ModBus register addresses are provided in Table 6-1.
Addr
Inst
R/W
Host
R/W
Range
Description
40101
R/W
R/W
MSB = $01 to
$FF
LSB = $01 to
$F7
Sensor Type
Holds the sensor instrument type code
and ModBus address. The most
significant byte (MSB) holds a value
indicating the type of instrument (see
below). The least significant byte (LSB)
holds a value which is the ModBus
address of the sensor.
MSB = Instrument type code $01 to $FF
$03 = IR (infrared)
$04 = TOX (toxic)
$05 = OXY (oxygen)
$06 = AAW (toxic)
$07 = CAT (catalytic)
LSB = MODBUS sensor address $01 to
$F7 (1 to 247)
40102
W
R
$0000 to $FFFF
Gas Reading
Holds the gas reading in ppm or percent
depending upon the sensor in the
instrument. The range is from $0000 to
$FFFF and represents a signed decimal
value range from -32768 to +32767.

Table of Contents

Related product manuals