EasyManuals Logo

Omega DP20 User Manual

Omega DP20
30 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #29 background imageLoading...
Page #29 background image
29
DP20 Economical Multisignal meter Instruction Manual
Protocol Modbus RTU
Bus type
RS-485, congurable for 9.600 or 4800 bps
Addresses 1 to 247
Formats congurable 8n1, 8e1, 8o1, 8n2
Funcons 4 read register
Registers 0 reading value (16 bits)
1 number of decimals (16 bits)
Errors 0 funcon not supported
1 register not accessible
Isolaon 1000 Vdc
Slots allowed Opt.1
2.3 Module S1 (Modbus RTU)
The S1 module oers 1 Modbus RTU serial output, isolated, to be
installed at slot Opt1.
Conguraon is done from the front keypad, through the conguraon
menu. The instrument must be informed that there is a Modbus RTU
module at slot.1 and this is done at the conguraon menu Tool’ \
out.1’ (see secon 1.28.7). Then congure the bus parameters at the
conguraon menu ‘out.1’ \ ‘r485’ (see secon 1.28.8).
The S1 module can be ordered installed in to a Series C instrument
or standalone for later installaon, as it does not require soldering or
special conguraon.
Terminal B B
Terminal A A
Terminal G GND
PowerSignal
Installing, calibrang and conguring a M1 module
If the M1 module has been acquired installed in the instrument, then
the module has been factory calibrated. In this case you can jump
directly to point 7 below.
If the M1 module has been acquired separately and installaon is
needed, follow the next steps :
1. Access the instrument and install the M1 module at slot Opt.1
(see secon 1.25).
2. From the ‘Conguraon menu’ go to ‘tool’ \ out.1’ and select
value ‘420’ (see secon 1.28.7) to inform the instrument that there
is a M1 analog output module installed.
From this point you will need the calibraon sheet provided together
with the module M1. This sheet shows the values for parameters
cAL.y / 4mA’ and ‘cAL.y / 20mA’.
3. When selecng ‘420’ the instrument shows cAL.n. (‘Do not
calibrate’). Press ‘UP’ (5) to read ‘cAL.y’ (‘Calibrate’).
4. When selecng cAL.y(‘Calibrate’) select ‘4 mA. Display shows
a number. Introduce the value of the ‘cAL.y / 4mA’ indicated at the
calibraon sheet provided together with the M1 module. Increase
the numerical value with key ‘UP’ (5) and reduce the value with
key ‘LE’ (3). Validate the value with key ‘SQ’ (<). See below an
image of the conguraon menu.
5. Repeat with the ‘20 mAparameter, and update with the value
cAL.y / 20mA indicated at the calibraon sheet. Validate with
key ‘SQ’ (<), and press key ‘LE’ (3) several mes to exit the
‘Conguraon menu’.
6. The instrument will reboot when exing the menu. The analog
output is calibrated.
Note : if you do not have the calibraon sheet which was shipped
together with the M1 module, you can use a miliammeter to
measure the mA at the output loop. Then access parameters
cAL.y / 4mA’ and ‘cAL.y / 20mAand adjust the calibraon value by
checking the miliammeter value.
At this point the module is installed and calibrated. Now congure
the reading associated to the output signal 4 mA and 20 mA.
7. Congure the reading associated to the 4 mA output signal
and the reading associated to the 20 mA output signal, at the
conguraon menu ‘out.1’ \ ‘420’ (see secon 1.28.8).
Do not calibrate
Calibrate
Opon 1
analog output
relay
Disabled
Tools
Modbus RTU
B A G
Opt.1
GND
B
A

Other manuals for Omega DP20

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omega DP20 and is the answer not in the manual?

Omega DP20 Specifications

General IconGeneral
BrandOmega
ModelDP20
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals