5
6
Input signal terminals
Jumpers ‘S’ for signal
range selecon
Displays
F
E
G
H
I
J
D
B
C
A
K
1.9 Internal jumpers
Internal jumpers ‘S’ are associated to the signal range. The posion of
internal jumper ‘T’ assigns the funcon of the mulfuncon terminal
5. At ‘Table 2’ see a list of signal ranges and associated jumper ‘S’
and ‘T’. At Table 3 see the posion for jumper ‘T’ associated to each
funcon of the mulfuncon terminal 5. To access the internal
jumpers, open the housing as explained at secon 1.25. For addional
informaon on each signal range see the following secons :
• Ranges for AC voltages and currents, see secon 1.10
• Ranges for DC voltages and currents, see secon 1.11
• Ranges for thermocouples, see secon 1.12
• Ranges for Pt and Ni probes, see secon 1.13
• Ranges for NTC probes, see secon 1.14
• Ranges for PTC probes, see secon 1.15
• Ranges for process signals, see secon 1.16
• Ranges for frequency signals, see secon 1.17
• Ranges for resistance measures, see secon 1.18
• Ranges for potenometer measures, see secon 1.19
Range Jumpers
‘S’
Jumper
‘T’
AC voltages and currents
~ 600 Vac
G I
4-5
~ 200 Vac
I
~ 20 Vac
A I
~ 2 Vac
B I
~ 200 mVac
C I
~ 60 mVac
E I
~ 5 Aac I
~ 20 mAac D I
DC voltages and currents
±600 Vdc
G
4-5
±200 Vdc
- - -
±20 Vdc
A
±2 Vdc
B
±200 mVdc
C
±60 mVdc
E
±5 Adc - - -
±20 mAdc D
Process
4/20 mA D
1-2
*
0/10 Vdc A
* jumper 1-2 to acvate Vexc.
Select 4-5 to acvate funcon ‘EK’
Resistances
0 to 5 K F H K
4-5
0 to 50 K F K
Table 2 - Jumpers ‘S’ and ‘T’ and signal
ranges
Range Jumpers
‘S’
Jumper
‘T’
Thermocouples
Tc. K
E
4-5
Tc. J
Tc. E
Tc. N
Tc. L
Tc. R
E J
Tc. S
Tc. T
Tc. C
E
Tc. B
E J
Pt and Ni probes
Pt100
(3 wire)
F H J 5-6
Pt100
(2 wire)
F H
4-5
Pt500 F
Pt1000 F
Ni100 F H
Ni200 F H
Ni1000 F
NTC probes
NTC F K 4-5
PTC probes
KTY 121 F
4-5
KTY 210, 220 F H K
Potenometers
0/100 % A 2-3
Table 2 - Jumpers ‘S’ and ‘T’ and signal
ranges
Jumpers stored at
‘no contact’ posion
F
E
G
H
I
J
D
B
C
A
K
Jumpers not used can be stored for
future use by placing them at the ‘no
contact’ posions indicated below.
Only the 3 posions indicated are
safe to store jumpers.
Jumpers ‘T’ Acve funcon at terminal 5
1 2 Vexc (excitaon voltage +15 Vdc) for process
2 3 Potenometer excitaon (+5 Vdc)
4 5 External control (‘EK’ funcon)
5 6 Pt100 third wire
Table 3 - Jumpers ‘T’ and funcon at mulfuncon terminal 5
2
1
3
5
4
6
Jumpers ‘T’ for terminal 5
funcon selecon