EasyManua.ls Logo

Omicron CP SB1 - Four-Wire Connection for Transformer Winding Resistance Measurement

Omicron CP SB1
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
63
Appendix
Figure 5-7 shows a diverter switch of a 40 MVA transformer for 110 kV. The
switches shown are positioned near the star-point of the transformer's high
voltage windings.
Figure 5-7 Diverter switch for 110 kV / 40 MVA
5.1.4 Four-Wire Connection for Transformer Winding Resistance
Measurement
Since the winding resistances are very small, the test set is connected in a four-
wire configuration. It has to be observed that the contact resistances of the
connection clamps do not falsify the measuring result.
A constant current source is used to feed a direct current into the winding. The
test current should be at least 1% of the rated current to bring the core into
saturation. On the other hand, it should not exceed 15% of the rated current to
avoid temperature rise during measurement. A relatively high no-load voltage
enables a quick saturation of the core and a final value with only minor
fluctuations is reached. Therefore, in most cases the charging time per tap is
distinctly less than 30 seconds.

Table of Contents