EasyManua.ls Logo

Omron B7A - Page 39

Omron B7A
121 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
B7A
B7A
37
Connection
of Single Power Supply to Input or Output T
erminal
Note:
In this example, a shielded transmis
-
sion cable with a thickness of 0.75 mm
2
min. is used, through which a current of
1.8 A max. can be transmitted. It is rec
-
ommended that the shield be grounded.
DC power
supply
– +
+
SIG
Transmission distance
50 m max.
(24 V)
SIG–+ERR
SIG–+
GND
Shielded cable
Input Output
32-point Terminal Models
I/O
Delay: Normal Speed
Connection of Independent Power Supplies
Note:
A VCTF cable with a
thickness of 0.75 mm
2
min. must be used for
signal transmission.
DC power
supply
– +
SIG2
Transmission distance
500 m max.
DC power
supply
– +
(12 to 24 V) (12 to 24 V)
SIG SIG
––
21
SIG SIG
21
ERRERR
21
SIG1
+
+––
Input Output
Connection
of Single Power Supply to Input or Output T
erminal
Note:
In this example, a
VCTF transmission
cable with a thickness
of 0.75 mm
2
min. is
used, through which a
current of 1.8 A max.
can be transmitted.
DC power
supply
– +
SIG2
Transmission distance
100 m max.
(12 to 24 V)
SIG SIG
––
21
SIG SIG
21
ERRERR
21
SIG1
+
+––
+
Input Output

Related product manuals