B7A
B7A
38
I/O
Delay: High Speed
Connection of Independent Power Supplies
Note:
A shielded cable with a
thickness of 0.75 mm
2
min. must be used for sig
-
nal transmission. It is rec
-
ommended that the shield
be grounded.
DC power
supply
– +
(12 to 24 V)
SIG SIG
––
21
SIG SIG
21
ERRERR
21
+
+––
Transmission distance
100 m max.
Shielded cable
SIG1
SIG2
GND
DC power
supply
– +
(12 to 24 V)
Input Output
Connection
of Single Power Supply to Input or Output T
erminal
Note:
In this example, a
shielded transmission
cable with a thickness of
0.75 mm
2
min. is used,
through which a current
of 1.8 A max. can be
transmitted. It is recom
-
mended that the shield
be grounded.
DC power
supply
– +
(24 V)
SIG SIG
––
21
SIG SIG
21
ERRERR
21
+
+––
Transmission distance
50 m max.
Shielded cable
SIG1
SIG2
GND
+
Input Output

Related product manuals