283
Water-resistant Terminals Section 5-4
Note The V terminals are all connected internally, as are the G terminals. Output
connectors G and V are available to external power supply, provided that the
total current flow through these connectors is less than 2.4 A when output
power supply is provided to the external power supply connector. Connect
external power supply if the total current flow is 2.4 A or more.
Dimensions
SRT2–OD04CL, SRT2-OD04CL-1
Mounting dimensions
Three, 5.3 dia. or M5 holes
(Unit: mm)