311
Analog Input Terminals Section 5-7
Node Number Setting
Set the node number with pins 5 through 8, as shown in the following table.
A single Analog Input Terminal is allocated 64 points, 48 points, 32 points, or
16 points. Points are assigned as shown in the following table. Note that when
a CQM1 Master Unit is used in 4-point mode, the Analog Input Terminal can-
not be connected.
Node number Pin 5
(8)
Pin 6
(4)
Pin 7
(2)
Pin 8
(1)
0 OFF OFF OFF OFF
1 OFF OFF OFF ON
2 OFF OFF ON OFF
3OFFOFFONON
4 OFF ON OFF OFF
5 OFF ON OFF ON
6 OFF ON ON OFF
7 OFF ON ON ON
8 ON OFF OFF OFF
9ONOFFOFFON
10 ON OFF ON OFF
11 ON OFF ON ON
12 ON ON OFF OFF
13 ON ON OFF ON
14 ON ON ON OFF
15 ON ON ON ON
Allocated points Node number setting Node number actually used
64 points
(4 inputs)
Odd Node number setting – 1 to node num-
ber setting + 6
Even Node number setting to node number
setting + 7
48 points
(3 inputs)
Odd Node number setting – 1 to node num-
ber setting + 4
Even Node number setting to node number
setting + 5
32 points
(2 inputs)
Odd Node number setting – 1 to node num-
ber setting + 2
Even Node number setting to node number
setting + 3
16 points
(1 input)
Odd Node number setting – 1 to node num-
ber setting
Even Node number setting to node number
setting + 1