Analog Output Terminals Section 5-8
Note Make sure that the communications mode of the Slave is the same as that of
the Master Unit. If the communications modes are not the same, normal com-
munications with the Master Unit will not be possible. The operating status of
the Slave can be verified with LED indicators. Refer to
6-5-1 Indicators for
details.
Node Number Setting
Set the node number with pins 5 through 8, as shown in the following table.
A single Analog Output Terminal is allocated either 32 points or 16 points.
Points are assigned as shown in the following table. Note that when CQM1
Master Unit is used in 4-point mode, an Analog Output Terminal cannot be
connected.
Pin 2 Number of output points setting
OFF 2 points (Factory setting)
ON 1 point (Output 0 valid)
Pin 3 Communications mode setting
OFF High-speed Communications Mode (Factory setting)
ON Long-distance Communications Mode
Pin 4 Always set to OFF.
Node number Pin 5
(8)
Pin 6
(4)
Pin 7
(2)
Pin 8
(1)
0 OFF OFF OFF OFF
1 OFF OFF OFF ON
2 OFF OFF ON OFF
3OFFOFFONON
4 OFF ON OFF OFF
5 OFF ON OFF ON
6 OFF ON ON OFF
7 OFF ON ON ON
8 ON OFF OFF OFF
9ONOFFOFFON
10 ON OFF ON OFF
11 ON OFF ON ON
12 ON ON OFF OFF
13 ON ON OFF ON
14 ON ON ON OFF
15 ON ON ON ON
Allocated points Node number setting Node number actually used
32 points
(2 outputs)
Odd Node number setting – 1 to node num-
ber setting + 2
Even Node number setting to node number
setting + 3
16 points
(1 output)
Odd Node number setting – 1 to node num-
ber setting
Even Node number setting to node number
setting + 1