Compatible Devices Section 1-3
Note 1. Connect a terminator (Connector Terminator, Shield Terminator, or Termi-
nal-block Terminator) to the following point in the system.
System with Distinction between Main and Branch Lines: The end of
the main line farthest from the Master.
System with No Distinction Main and Branch Lines: The end of the
communications cable farthest from the Master.
2. Use a commercially available terminal block or T-joint to branch or extend
VCTF cable.
Connector Socket Assembly
(female for screw, crimp, sol-
der terminals)
XS2C-D4S7 A connector used to connect to the communi-
cations connector or external power supply
connector of the Water-resistant Terminal or a
T- j o i n t p l u g .
Applicable cable dia.: 6 to 8 mm
Applicable conductor size: 0.18 to 0.75 mm
2
XS2C-D4@@ A connector used to connect to the external
power supply connector of the Water-resistant
Terminal or a T-joint plug.
Applicable cable dia.: 3 to 6 mm
Applicable conductor size: 0.18 to 0.3 or 0.5
to 0.75 mm
2
Connector Plug Assembly
(male for screw, crimp, solder
terminals)
XS2G-D4S7 A connector used to connect to the T-joint
socket.
Applicable cable dia.: 6 to 8 mm
Applicable conductor size: 0.18 to 0.75 mm
2
XS2G-D4@@ A connector used to connect to the I/O con-
nector of the Water-resistant Terminal or a T-
joint socket.
Applicable cable dia.: 3 to 6 mm
Applicable conductor size: 0.18 to 0.3 or 0.5
to 0.75 mm
2
T-joint XS2R-D427-5 A joint used to T-branch a VCTF cable (e.g., a
communications cable or power supply
cable).
Communications Connector
(6 pins)
FK-MCP1.5/6-STF-
3.81
A communications connector for connecting
CJ-series Master Units. The connector can be
connected simultaneously to the communica-
tions cable (BD H, BD L, BS+, BS–) and com-
munications power supply (BS+, BS–).
This connector has screwless terminals for
signal lines and connector lock screws.
MC1.5/6-STF-3.81 A communications connector for connecting
CJ-series Master Units. The connector can be
connected simultaneously to the communica-
tions cable (BD H, BD L, BS+, BS–) and com-
munications power supply (BS+, BS–).
This connector has screw terminals for signal
lines and connector lock screws.
Shielded Terminator Plug
(Male)
SRS2-1 A shielded connector terminator model con-
nected to a T-joint.
Terminal-block Terminator SRS1-T This terminal block has a built-in terminator.
(Can be used with VCTF cable and Special
Flat Cable.)
Connector Model Comments