45
I/O Response Time Characteristics Section 2-5
T
M-in-max
:Maximum input processing time in the Master
CS-series, C200HX/C200HG/C200HE-(Z)E, and C200HS Master
Units
CS-series Master Units
Note Add another 15
µs to the values in the table when using the Slave
registration function or communications stop mode.
CJ-series Master Units
Note Add another 15
µs to the values in the table when using the Slave
registration function or communications stop mode.
CQM1 Master Units
T
M-out-max
:Maximum output processing time in the Master
CS-series, C200HX/C200HG/C200HE-(Z)E, and C200HS Master
Units
CS-series Master Units
Note Add another 15
µs to the values in the table when using the Slave
registration function or communications stop mode.
Master Number of points/
node number
Max. input pro-
cessing time
CS Series, C200HX/
C200HG/ C200HE-(Z)E,
and C200HS
--- 470 µs
Master Usable node number setting
IN0 to IN7 and OUT0
to OUT7
IN0 to IN15 and
OUT0 to OUT15
CS1 (without -H suffix) T
M-in-max
= 270 µsT
M-in-max
= 320 µs
CS1-H T
M-in-max
= 220 µsT
M-in-max
= 270 µs
Master Usable node number setting
IN0 to IN7 and OUT0
to OUT7
IN0 to IN15 and
OUT0 to OUT15
CJ1 (without -H suffix) T
M-in-max
= 270 µsT
M-in-max
= 320 µs
CJ1-H T
M-in-max
= 220 µsT
M-in-max
= 270 µs
Master Number of points/
node number
Max. input pro-
cessing time
CQM1 8-point mode 300 µs
4-point mode 860 µs
Master Number of points/
node number
Max. output pro-
cessing time
CS-series, C200HX/
C200HG/ C200HE-(Z)E,
and C200HS Masters
--- 650 µs
Master Usable node number setting
IN0 to IN7 and OUT0
to OUT7
IN0 to IN15 and
OUT0 to OUT15
CS1 T
M-out-max
= 100 µsT
M-out-max
= 130 µs

Table of Contents