EasyManua.ls Logo

Omron C200HW-SRM21-V1 - 08-2007 - Page 73

Omron C200HW-SRM21-V1 - 08-2007
423 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
52
I/O Response Time Characteristics Section 2-5
Note 1. This is the ON response time for the SRT@-ROC@@
2. This is the OFF response time for the SRT@-ROF@@
Maximum Input Delay
Time for Fiber Amplifier
Communications Unit
For up to 8 sensors connected:
Maximum ON/OFF data input delay time for unit n = 0.1
× n +1.5 (ms)
For 9 sensors or more connected:
Maximum ON/OFF data input delay time for unit n = 0.2
× n +1.5 (ms)
SRT2-ND08S 4-point input, 4-point output sensor
terminal
1 ms max. 1.5 ms max. 1.0 ms max. 1.5 ms max.
SRT1-OD08S 8-point output sensor terminal --- --- 0.5 ms max. 1.5 ms max.
SRT2-OD08S 8-point output sensor terminal --- --- 0.5 ms max. 1.5 ms max.
SRT2-ID04CL(-1) 4-point input water-resistant termi-
nal
1.5 ms max. 1.5 ms max. --- ---
SRT2-ID08CL(-1) 8-point input water-resistant termi-
nal
1.5 ms max. 1.5 ms max. --- ---
SRT2-OD04CL(-1) 4-point output water-resistant termi-
nal
--- --- 0.5 ms max. 1.5 ms max.
SRT2-OD08CL(-1) 8-point output water-resistant termi-
nal
--- --- 0.5 ms max. 1.5 ms max.
E3X-SRT21 8-point/16-point input Fiber Ampli-
fier Communications Unit
See below. --- ---
Model Specifications Input specifications Output specifications
ON delay time OFF delay
time
ON delay
time (See
note 1.)
OFF delay
time (See
note 2.)

Table of Contents