PLC Setup Section 7-1
Baud Rate (bps)
NT Link Max. (Maximum Unit Number in NT Link Mode
)
Peripheral Bus Settings
Communications Settings
Mode: Communications Mode
Address in
Programming
Console
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
161 0 to 7 00: Standard
0A: High-speed NT
Link*
Default: 00
* Set to 115,200 bps when setting this value
from the CX-Programmer. To return to the
standard setting, leave the setting set to
“PLC Setup” and set the baud rate to 9,600
bps.
A61902
(RS-232C
Port Settings
Changing
Flag)
At the next
cycle.
Address in
Programming
Console
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
166 0 to 3 0 to 7
Default: 0
This setting determines the highest unit
number of PT that can be connected to the
PLC.
A61902
(RS-232C
Port Settings
Changing
Flag)
At the next
cycle.
Address in
Programming
Console
Settings Function Related
flags and
words
When set-
ting is
read
by CPU Unit
Word Bit(s)
160 15
0: Standard*
1: PLC Setup (cus-
tom)
Default: 0
*The default settings are for a baud rate of
9,600 bps.
A61902
(RS-232C
Port Settings
Changing
Flag)
At the next
cycle.
Address in
Programming
Console
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
160 8 to 11 04: Peripheral bus
Default: 0
This setting determines whether the RS-
232C port will operate in host link mode or
another serial communications mode. (Host
link can be specified with 00 or 05.)
The Peripheral Bus mode is for communica-
tions with Programming Devices other than
the Programming Console.
A61902
(RS-232C
Port Settings
Changing
Flag)
At the next
cycle.