PLC Setup Section 7-1
Baud Rate (bps)
Serial PLC Link (CJ1M CPU Units Only)
Polling Unit: Serial Communications Mode
Polling Unit: Port Baud Rate
Note Set to 115,200 bps when using the CX-Programmer
Polling Unit: Link Method
Address in
Programming
Console
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
161 0 to 7 00: 9,600 bps
06: 9,600 bps
07: 19,200 bps
08: 38,400 bps
09: 57,600 bps
0A: 115,200 bps
Default: 00
Settings 00 and 06 through 0A are valid
when the communications mode is set to
peripheral bus.
A61902
(RS-232C
Port Settings
Changing
Flag)
At the next
cycle.
Address in
Programming
Console
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
160 8 to 11 8: Serial PLC Link
Polling Unit
Default: 0
This setting specifies the serial communica-
tions mode that the RS-232C port is to be
used with. It also designates the local node
as the Serial PLC Link Polling Unit.
A61902
(RS-232C
Port Settings
Changing
Flag)
At the next
cycle.
Address in
Programming
Console
Settings Function Related
flags and
words
When s
et-
ting is read
by CPU Unit
Word Bit(s)
161 0 to 7 00: Standard
0A: High-speed
(See note.)
Default: 00
This setting specifies the Serial PLC Link
baud rate.
Note: The setting must be the same for all of
the Polled Units and the Polling Unit using
the Serial PLC Links.
A61902
(RS-232C
Port Settings
Changing
Flag)
At the next
cycle.
Address in
Programming
Console
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
166 15 0: Complete link
method
1: Polling Unit link
method
Default: 0
This setting specifies the link method for the
Serial PLC Link.
A61902
(RS-232C
Port Settings
Changing
Flag)
At the next
cycle.