281
PLC Setup Section 7-1
Delay
Serial Gateway Settings
Communications Settings
Mode: Communications Mode
Data Bits
Address in
Programming
Console
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
162 0 to 15 0000 to 270F: 0 to
99990 ms (10-ms
units)
Default: 0000
This setting determines the delay from exe-
cution of TXD(236) until the data is actually
transmitted from the specified port.
A61902
(RS-232C
Port Settings
Changing
Flag)
At the next
cycle.
(Also can be
changed with
STUP (237).)
Address in
Programming
Console
Settings Function Related
flags and
words
New set-
ting’s effec-
tiveness
Word Bit(s)
160 15 0: Default (stan-
dard)*
1: PLC Setup (cus-
tom)
Default: 0
*The default settings are for a baud rate of
9,600 bps.
A61901
(RS-232C
Port Settings
Changing
Flag)
Takes effect
the next
cycle.
(Also can be
changed with
STUP (237).)
Address in
Programming
Console
Settings Function Related
flags
and
words
New set-
ting’s effec-
tiveness
Word Bit(s)
160 8 to 11 9: Serial Gateway
Default: 0
This setting determines whether the com-
munications mode for the RS-232C port
port.
The peripheral bus mode is used for all Pro-
gramming Devices except for Programming
Consoles.
A61901 (RS-
232C Port
Settings
Changing
Flag)
Takes effect
the next
cycle.
(Also can be
changed with
STUP (237).)
160 8 to 11 0: Host Link
5: Host Link
Default: 0
This setting determines whether the com-
munications mode for the RS-232C port.
(Host Link can be used when specified to
either 0 or 5 hex.)
A61901 (RS-
232C Port
Settings
Changing
Flag)
Takes effect
the next
cycle.
(Also can be
changed with
STUP (237).)
Address in
Programming
Console
Settings Function Related
flags and
words
New set-
ting’s effec-
tiveness
Word Bit(s)
160 3 0: 7 bits
1: 8 bits
Default: 0
These settings are valid when the RS-232C
Port Settings Selection is set to 1: PLC
Setup.
A61901
(RS-232C
Port Settings
Changing
Flag)
Takes effect
the next
cycle.
(Also can be
changed with
STUP (237).)