282
PLC Setup Section 7-1
Stop Bits
Parity
Baud Rate (bps)
Response Monitoring Time
Address in
Programming
Console
Settings Function Related
flags and
words
New set-
ting’s effec-
tiveness
Word Bit(s)
160 2 0: 2 bits
1: 1 bit
Default: 0
These settings are valid when the RS-232C
Port Settings Selection is set to 1: PLC
Setup.
A61901
(RS-232C
Port Settings
Changing
Flag)
Takes effect
the next
cycle.
(Also can be
changed with
STUP (237).)
Address in
Programming
Console
Settings Function Related
flags and
words
New set-
ting’s effec-
tiveness
Word Bit(s)
160 0 to 1 00: Even
01: Odd
10: None
Default: 00
These setting is valid only when the commu-
nications mode is set to Host Link.
These settings are also valid only when the
RS-232C Port Settings Selection is set to 1:
PLC Setup.
A61902
(RS-232C
Port Settings
Changing
Flag)
Takes effect
the next
cycle.
(Also can be
changed with
STUP (237).)
Address in
Programming
Console
Settings Fun
ction Related
flags and
words
New set-
ting’s effec-
tiveness
Word Bit(s)
161 0 to 7 00: 9,600
01: 300
02: 600
03: 1,200
04 2,400
05: 4,800
06: 9,600
07: 19,200
08: 38,400
09: 57,600
0A: 115,200
Default: 00
These setting is valid only when the commu-
nications mode is set to Host Link.
These settings are also valid only when the
RS-232C Port Settings Selection is set to 1:
PLC Setup.
A61902
(RS-232C
Port Settings
Changing
Flag)
Takes effect
the next
cycle.
(Also can be
changed with
STUP (237).)
Address in
Programming
Console
Settings Function Related
flags and
words
New set-
ting’s effec-
tiveness
Word Bit(s)
161 8 to 15 00: 5 s
01 to FF: 100 to
25,500 ms (Unit:
100 ms)
Default: 00
Monitors the time from when the FINS com-
mand that has been converted into the
specified protocol using Serial Gateway is
sent until the response is received.
Default: 5 s; PLC Setup: 0.1 to 25.5 s
Note: If a timeout occurs, the FINS end
code 0205 hex (response timeout) will be
returned to the FINS source.
A61902
(RS-232C
Port Settings
Changing
Flag)
Takes effect
the next
cycle.
(Also can be
changed with
STUP (237).)