284
PLC Setup Section 7-1
Format: Parity
Mode: Communications Mode
Unit Number (for CPU Unit in Host Link Mode
)
NT Link Settings
Mode: Communications Mode
Baud Rate (bps)
Address in
Programming
Console
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
144 0 and 1 00: Even
01: Odd
10: None
Default: 00
These setting is valid only when the commu-
nications mode is set to Host link.
These settings are also valid only when the
Peripheral Port Settings Selection is set to
1: PLC Setup.
A61901
(Peripheral
Port Settings
Changing
Flag)
At the next
cycle.
(Also can be
changed with
STUP (237).)
Address in
Programming
Console
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
144 8 to 11 00: Host Link
05: Host link
Default: 0
This setting determines whether the periph-
eral port will operate in host link mode or
another serial communications mode. (Host
link can be specified with 00 or 05.)
The Peripheral Bus Mode is for communica-
tions with Programming Devices other than
the Programming Console.
A61901
(Peripheral
Port Settings
Changing
Flag)
At the next
cycle.
(Also can be
changed with
STUP (237).)
Address in
Programming
Console
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
147 0 to 7 00 to 1F
(0 to 31)
Default: 00
This setting determines the CPU Unit’s unit
number when it is connected in a 1-to-N
(N=2 to 32) Host Link.
A61901
(Peripheral
Port Settings
Changing
Flag)
At the next
cycle.
(Also can be
changed with
STUP (237).)
Address in
Programming
Console
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
144 8 to 11 02: 1:N NT Link
Default: 0
This setting determines whether the RS-
232C port will operate in host link mode or
another serial communications mode.
Note Communications will not be possible
with PTs set for 1:1 NT Links.
A61902
(RS-232C
Port Settings
Changing
Flag)
At the next
cycle.
(Also can be
changed with
STUP (237).)
Address in
Programming
Console
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
145 0 to 7 00: Standard
0A: High-speed NT
Link*
Default: 00
* Set to 115,200 bps when setting this value
from the CX-Programmer.
A61901
(Peripheral
Port Settings
Changing
Flag)
At the next
cycle.
(Also can be
changed with
STUP (237).)