EasyManua.ls Logo

Omron CJ1W-DA08C

Omron CJ1W-DA08C
427 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
381
Data Memory Coding Sheets Appendix C
Mean Value Processing Setting
0000: Mean value processing for 2 buffers
0001: No mean value processing
0002: Mean value processing for 4 buffers
0003: Mean value processing for 8 buffers
0004: Mean value processing for 16 buffers
0005: Mean value processing for 32 buffers
0006: Mean value processing for 64 buffers
Conversion Time/Resolution or Operation Mode Setting
Scaling data
32000 to +32000
Voltage/current range setting (Only for 1 to 5 V and 4 to 20 mA.)
0: Voltage
1: Current
15 to 12 11 to 08 07 to 04 03 to 00
16
3
16
2
16
1
16
0
15 to 12 11 to 08 07 to 04 03 to 00
16
3
16
2
16
1
16
0
00: Conversion time
= 1 ms /resolution of
4,000
C1: Conversion time
= 1 ms /resolution of
4,000
00: Normal mode
01: Adjustment mode
07 06 05 04 03 02 01 00
Input
8
Input
7
Input
6
Input
5
Input
4
Input
3
Input
2
Input
1
15 14 13 12 11 10 09 08
Input
16
Input
15
Input
14
Input
13
Input
12
Input
11
Input
10
Input
9

Table of Contents

Related product manuals