EasyManua.ls Logo

Omron CJ1W-DRM21 - Page 163

Omron CJ1W-DRM21
350 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-23
4 Remote I/O Master Communications
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit(W497)
4-4 User-set Allocations
4
4-4-1 Settings through CX-Integrator
Step 1
Set the area, start word, and words allocated for each block with the use of the CX-Integrator.
Step 2
Allocate words to all node addresses in each block as shown below with the use of the CX-Integra-
tor.
Each address is allocated at least one byte (rightmost or leftmost byte).
Note a) You can set the order of all blocks as you desire.
b) Node addresses do not have to correspond between an output block and input block.
c) The same node address cannot be allocated more than once.
Allocation Procedures
OUT block 1
Node address 00
Node address 03
Node address 00: DRT1-OD16 (16 output pts)
Node address 03: DRT2-DA02 (2 analog output points = 32 bits)
IN block 1
Node ad-
dress 02
Node address 01: DRT1-ID08 (8 input pts)
Node address 02: DRT1-ID08 (8 input pts)
Node ad-
dress 01
IN block 2
OUT block 1
OUT block 2
IN block 1
OUT block 1
Node address 01
Node address 02
Node address 03
IN block 1
Node address 01
Node address 02
This is not necessary.Example:
Example:
OUT block 1
Node address 02
OUT block 2
Node address 02

Table of Contents

Related product manuals