9 Troubleshooting and Maintenance
9-14
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit(W497)
*1 The 7-segment indicator will alternate between the Unit's node address and the code given in the tables in this section.
*2 The NS indicator will flash red if the error occurs during remote I/O communications, otherwise the indicator will be OFF.
Indicators Error
category
Error Likely cause DeviceNet Unit
response
Error
log
(Hex)
MS NS 7-seg-
ment
*1
- OFF or
Red
(flashing)
*2
E2 Network Transmis-
sion time-
out error
A transmission request
was not completed nor-
mally for one of the follow-
ing reasons:
There is not even one
device such as a slave in
the network.
The communications
speed settings are not
the same in all of the
nodes.
CAN controller error
As long as transmission
timeout is in effect, remote
I/O communications will
remain stopped and errors
will be returned in
response to requests for
message transmissions.
The indicator status, scan-
ning, and message pro-
cessing will return to
normal when the transmis-
sion timeout returns to nor-
mal, although scanning will
not resume if the
DeviceNet Unit is set to
stop remote I/O communi-
cations when a communi-
cations error occurs.
0342
Red
(flashing)
- E6 Memory
access
Message
monitoring
timer list
logic error
There is an error in the
contents of the message
monitoring timer list stored
in non-volatile memory.
Records the error in the
error log.
Operation will continue
using the default message
monitoring timer values.
021A
Red
(flashing)
- E7 Slave scan
list logic
error
There is an error in the
contents of the slave scan
list stored in non-volatile
memory.
Records the error in the
error log.
The slave remote I/O
communications will be
stopped.
Message processing
and the exchange of
data with the CPU Unit
will continue. Normal
operation will resume
when the slave scan list
is written normally. (Start
the slave remote I/O
communications.)
021A