A-45
Appendices
CP1E CPU Unit Hardware User’s Manual(W479)
A-3 Wiring for Serial Communications
App
A-3-3 Converting the Built-in RS-232C Port to
RS-422A/485
• Four-wire Connections
Use one of the following Conversion Units to convert a built-in RS-232C port to an RS-422A port for a
CP1E N/NA-type CPU Unit.
• CJ1W-CIF11 RS-422A Conversion Unit
Maximum distance: 50 m, convertible to RS-422A or RS-485.
• NT-AL001 RS-232C/RS-422A Conversion Unit:
Maximum distance: 500 m, convertible to RS-422A only.
Note CJ1W-CIF11 cannot be connected to the built-in RS-232C port of the CP1E NS(1)-type CPU Unit.
The CJ1W-CIF11 RS-422A Conversion Unit is used to convert an RS-232C port to RS-422A/485.
It is directly connected to the built-in RS-232C port of the CP1E N/NA-type CPU Unit.
The Conversion Unit is not insulated, so the maximum distance for RS-422A/485 is 50 m.
Note CJ1W-CIF11 cannot be connected to the built-in RS-232C port of the CP1E NS(1)-type CPU Unit.
z Appearance
z Electrical Specifications
• RS-422A/485 Terminal Block
• RS-232C Connector
A-3-3 Converting the Built-in RS-232C Port to RS-422A/485
CJ1W-CIF11 RS-422A Conversion Unit
Signal
RDA-
RDB+
SDA-
SDB+
FG
Pin Signal
1FG
2RD
3SD
4CS
5RS
6+5V
7,8 NC
9SG(0V)
Hood NC*
SDA-
SDB+
RDA-
RDB+
FG
3
4
1
2
5
RDA
RDB
SDA
SDB
FG
CP1E N/NA-type CPU Unit
RS-422A/485 Option Board
Pin Signal Signal
Shield
Remote device
Ground the shield at one end
when using CP1W-CIF12.
RDA- RDB+ SDA- SDB+ FG
RDA-
RDB+
SDA-
SDB+
FG
+5V 6
– 7
– 8
SG(0V) 9
1 FG
2 RD
3 SD
4 CS
5 RS
RS-232C port Connector pin
arrangement