1 Overview and Specifications
1-2
CP1E CPU Unit Hardware User’s Manual(W479)
1-1 CP1E Overview
The SYSMAC CP1E Programmable Controller is a package-type PLC made by OMRON that is designed
for easy application. The CP1E includes E(S)-type CPU Units (basic models) for standard control
operations using basic, movement, arithmetic, and comparison instructions, and N/NA(S)-type CPU
Units (application models) that supports connections to Programmable Terminals, Inverters, and Servo
Drives.
1-1-1 Overview of Features
Basic Models CP1E Application Models
E(S)-type CPU Units N(S)-type CPU Units
NA-type
CPU Units
CPU with 10, 14
or 20 I/O Points
CPU Unit with 30, 40 or
60 I/O Points
CPU with 14 or
20 I/O Points
CPU Unit with
30, 40 or 60 I/O
Points
CPU Unit with
20 I/O Points
Appearance E-type
ES-type
E-type
ES-type
N-type N/NA-type
NS(1)-type
I/O points E 10/14/20/30/40
ES 14/20/30/40/60
N 14/20/30/40/60
NS(1) 30/40/60
20
Program capacity 2K steps 8K steps
DM Area capacity 2K words
Of these 1,500 words can be written to the
built-in EEPROM.
8K words
Of these 7,000 words can be written to the built-in
EEPROM.
Mounting Expan-
sion I/O Units and
Expansion Units
Not possible. 3 Units maximum Not possible. 3 Units maximum
Model with transis-
tor outputs
Available (CPU Unit with 10 I/O points only) Available
Pulse outputs Not supported. Supported (Model with transistor outputs only)
Built-in serial com-
munications port
Not provided. RS-232C port provided
RS-485 port provided (NS1-type only)
Built-in analog Not available. Not available. Available
Option Board Not supported. Not supported. N/NA-type: Supported (for one
port)
NS(1)-type: Not Supported
Connection port for
Programming Device
USB port USB port
Clock Not provided. Provided
Using a Battery Cannot be used. Can be used (sold separately).
Backup time of
built-in capacitor
50 hours at 25°C 40 hours at 25°C
Battery-free opera-
tion
Always battery-free operation.
Only data in the built-in EEPROM will be retained
if power is interrupted for longer than 50 hours.
Battery-free operation if no battery is attached. Only
data in the built-in EEPROM will be retained if power is
interrupted for longer than 40 hours.