274
Pulse Outputs Section 5-3
PLC Setup
Ladder Program
Function Setting (example)
Pulse Output 0 Origin Search Function Enable/Disable 1 hex: Enabled
Pulse Output 0 Origin Search Operating Mode 1 hex: Mode 1
Pulse Output 0 Origin Search Operation Setting 0 hex: Reverse mode 1
Pulse Output 0 Origin Detection Method 0 hex: Origin detection method 0
Pulse Output 0 Origin Search Direction Setting 0 hex: CW direction
Pulse Output 0 Origin Search/Return Initial Speed 0064 hex (100 pps)
0000 hex
Pulse Output 0 Origin Search High Speed 07D0 hex (2,000 pps)
0000 hex
Pulse Output 0 Origin Search Proximity Speed 03E8 hex (1,000 pps)
0000 hex
Pulse Output 0 Origin Compensation 0000 hex
0000 hex
Pulse Output 0 Origin Search Acceleration Rate 0032 hex (50 Hz/4 ms)
Pulse Output 0 Origin Search Deceleration Rate 0032 hex (50 Hz/4 ms)
Pulse Output 0 Limit Input Signal Type 1: NO
Pulse Output 0 Origin Proximity Input Signal Type 1: NO
Pulse Output 0 Origin Input Signal Type 1: NO
@ORG
#0000
#0000
CW limit detection
sensor
1.06
CW Limit
Input Signal
1.07
CCW limit
detection sensor
A540.08
CCW Limit
Input Signal
A540.09
Execution condition
Origin search 0:
#0000; Origin
search and
CW/CCW
method: #0000