394
Analog Input Units Section 7-2
■ 0 to 10 V Inputs
When the resolution is 1/6,000, the 0 to 10 V range corresponds to hexadeci-
mal values 0000 to 1770 (0 to 6,000). The range of data that can be converted
is FED4 to 189C hex (–300 to 6,300).
A negative voltage is expressed as two’s complement.
When the resolution is 1/12,000, the 0 to 10 V range corresponds to hexadec-
imal values 0000 to 2EE0 (0 to 12,000). The entire data range is FDA8 to
3138 hex (–600 to 12,600).
A negative voltage is expressed as a two’s complement.
■ 0 to 5 V Inputs
When the resolution is 1/6,000, the 0 to 5 V range corresponds to hexadeci-
mal values 0000 to 1770 (0 to 6,000). The range of data that can be converted
is FED4 to 189C hex (–300 to 6,300).
A negative voltage is expressed as two’s complement.
0V 10V
11V
−11V −10V
E890 (−6000)
E638 (−6600)
19C8 (6600)
1770 (6000)
0000 (0)
Converted Data
Hexadecimal (Decimal)
0 V 10 V
10.5 V
−0.5 V
Converted data
Hexadecimal (Decimal)
189C (6300)
1770 (6000)
0000 (0)
FED4 (−300)
0 V 10 V
10.5 V
−0.5 V
FDA8 (−600)
3138 (12600)
2EE0 (12000)
0000 (0)
Converted Data
Hexadecimal (Decimal)